Frequency-Dependent Winding Resistance: Fit the Complex Impedance and Check Causality

  • Chenfan Power

Fit frequency-dependent winding resistance as part of a realizable complex impedance. Retain loss, phase, poles and the zero-state response together when converting frequency data into a transient model.

Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.

The practical decision is whether the chosen model reproduces the intended conductor loss and phase over a declared band without responding before excitation. That requires more than fitting the real part accurately.

Preserve the quantity that was characterized

State whether the data are a conductor-path impedance, a closed-loop impedance or a terminal response containing capacitance and other structures. Those quantities do not have interchangeable resistance functions.

For a stated one-port convention, write Z(jω) = R(ω) + jX(ω), with voltage and current directions chosen consistently. Keep both parts and their units, frequency axis and temperature. Removing the reactive component changes the response, even when the dissipative curve remains unchanged.

Resolve conductor and return geometry before fitting frequency-dependent winding impedance. Cross-sectional current redistribution changes both resistive and reactive response; preserve the complex data across the study band.

Fit a realizable complex response

Use a stable rational realization and inspect its passive energy boundary. A nonnegative sampled real part alone cannot establish a causal complex impedance.

For a real physical response, conjugate poles and residues must be paired appropriately. A finite-dimensional causal rational model also needs a declared realization and treatment of its direct or derivative terms. Stable poles describe decaying modes; they do not excuse a noncausal frequency-domain operation elsewhere in the processing chain.

For a scalar impedance, nonnegative Re Z(jω) is a necessary sinusoidal dissipation check under the declared convention. A sampled real-part check does not independently prove causality, global passivity or accuracy outside the sampled band. Multiport checks additionally depend on the Hermitian dissipative matrix and port directions.

Construct a passive analytical benchmark

Use an original hypothetical one-port with R_0 = 0.1 Ω, a = 0.4 Ω and p = 1,000 s⁻¹:

Z(s) = R_0 + a s/(s + p).

It is realizable as R_0 in series with a parallel resistor a and inductor L = a/p = 400 µH. Positive resistances dissipate energy and the ideal inductor stores ½ L i_L². This manufactured circuit is not a calibrated winding model.

The only finite pole is −1,000 s⁻¹. With s = jω:

Re Z = R_0 + a ω²/(p² + ω²)

Im Z = a p ω/(p² + ω²).

Thus the real part rises from 0.1 toward 0.5 Ω, while the reactive part rises and then falls. The shared p connects their frequency behavior. The crossover angular frequency is p, corresponding to 159.155 Hz, not 1,000 Hz.

Angular frequency ωFrequency fRe ZIm Z
100 s⁻¹15.915 Hz0.103960 Ω0.039604 Ω
1,000 s⁻¹159.155 Hz0.300000 Ω0.200000 Ω
10,000 s⁻¹1,591.549 Hz0.496040 Ω0.039604 Ω

These values provide a reproducible implementation check, not skin-effect coefficients for a particular conductor.

Test the declared zero-state response

For a 1 A ideal current step starting at t = 0, with zero initial inductor current, inverse transformation gives:

v(t) = 0 for t < 0; v(t) = R_0 + a exp(−pt) for t ≥ 0.

The voltage jumps to 0.5 V and decays toward 0.1 V. At 1 ms it is 0.247152 V. Its impulse response contains an instantaneous term plus a causal decaying term; neither produces an output before the input.

The ideal step and full analytical frequency function make this a mathematical benchmark. They do not demonstrate an actual winding’s unlimited-bandwidth response or reproduce a measurement instrument’s finite rise time.

Expose the real-only counterexample

Now discard Im Z and use the even, real frequency multiplier Z_bad(jω) = Re Z(jω) over the complete mathematical frequency axis. It has exactly the same nonnegative resistance curve as the valid model.

For the Fourier convention paired with e^{jωt}, its impulse response is:

h_bad(t) = (R_0 + a) δ(t) − (a p/2) exp(−p|t|).

The exponential exists for negative time. Convolving with the same 1 A step produces a pre-input voltage −(a/2) exp(pt) for t < 0. At −1 ms, that voltage is −0.073576 V, while the causal circuit’s voltage is zero.

For t ≥ 0, the defective output is R_0 + (a/2) exp(−pt), giving 0.173576 V at 1 ms. This explicitly demonstrates how a perfect real-part match can still describe the wrong transient operation.

Exact invented RL impedance real and imaginary curves and causal versus real-only step responses, including a pre-input voltage counterexample.
Original manufactured impedance and exact step-response comparison. Both frequency multipliers have the same nonnegative real part, but retaining only that part over the complete analytical spectrum creates a two-sided impulse response and anticipates the input. Values are not winding measurements.

The counterexample discards phase over a specified complete analytical spectrum. It does not imply that a finite measured resistance band uniquely determines its missing phase, or that every numerical negative-time sample is physical evidence of noncausality.

Separate model causality from processing artifacts

A finite-band inverse transform can show ringing or apparent pre-response because of windowing, truncated bandwidth and periodic numerical extension. Measurement delays and de-embedding can also change the inferred time origin.

Check the rational realization and its declared zero-state simulation alongside the sampled transform. Preserve the instrument delay convention and explain any time shift. Do not fix an anticipatory response by silently shifting the curve until it looks causal.

For fitted data, reserve complex frequency samples for validation, including transition regions where skin/proximity behavior or resonances change rapidly. Compare impedance and a defined transient observable across reasonable model orders. Record the supported band and avoid using an ideal step as proof of out-of-band accuracy.

Release the complex data, fitting weights, pole list, passivity and causality checks, fixture treatment and input rise-time assumptions. State the validated band and compare a defined transient observable so both loss and phase remain supported by the same evidence.

Ruehli reconstructs closed-loop inductance from signed interactions between conductor segments. Retain the complete return path and current orientation before using a coefficient in the winding circuit. [1]

Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [2]

References

[1] A. E. Ruehli, Inductance Calculations in a Complex Integrated Circuit Environment, 1972, DOI:10.1147/rd.165.0470.

[2] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.