Document core-to-ground paths before the active part moves. Lifting, displaced insulation and changed clamp contact can remove an original conductive path or create a new one, changing the meaning of the subsequent resistance test. [1]

Map intended and possible paths separately
Document the designed intentional ground, accessible leads and their identification. On a separate layer, map suspected unintended contacts between core-related structures and grounded parts. Do not count every metallic structure as electrically continuous without confirming the construction.
Photograph contact regions with their neighboring insulation and support geometry. Record whether a visible mark was present before movement and whether an emergency intervention has already changed it.
| Ground-map entry | Required record |
|---|---|
| Intentional ground | Original termination, lead identity and documented connection state |
| Suspected contact | Location, surfaces and mechanical constraint |
| As-found electrical observation | Test boundary, equipment state and method |
| Intervention | What moved, disconnected or changed |
| Later observation | New boundary and difference from the original condition |
Preserve the test boundary
A core-to-ground resistance result must identify which connections remained present. An intentional ground in circuit changes the meaning of that measurement. The Bureau of Reclamation diagnostic guide distinguishes intentional grounding in its core-insulation test discussion; the historical procedure and numerical limits are not universal instructions for every transformer.
Use an approved test plan on safely isolated equipment for any temporary grounding change. Record the connection state before and after that intervention so the electrical result remains tied to the physical configuration.
Keep each ground observation linked to the physical configuration and documented intervention [2]. The same core can show a different resistance after a clamp moves; preserve the electrical boundary as well as the item identity.
Separate an unintended-loop loss from the steel baseline
Nippon Steel specifies maximum strip loss of 0.85 W/kg for 23ZH85 at 1.7 T, 50 Hz [3]. Assume an identified 1,000 kg population, giving an 850 W strip basis, and an unintended loop carrying 10 A RMS through 0.2 Ω at its stated temperature. Loop dissipation is 20 W. This separate loss does not identify changed steel quality. In a separate measurement-boundary example, assume three parallel paths: intentional bond 0.1 Ω, unintended contact 1,000 Ω and insulation 100 MΩ. Their combined reading is about 0.09999 Ω. In the approved test state with only the intentional path isolated, it becomes 999.99 Ω; if lifting removes the unintended contact, it becomes 100 MΩ. These assumptions demonstrate why the connection and movement record must accompany each result [1]. Resistance alone does not supply the assumed loop current.
Clamp insulation, fastener sleeves, deliberate bonding and metal-particle clearance control possible parallel paths. Joint fit, rolling direction and assembly pressure control the magnetic baseline independently. Record those construction states when interpreting a later ground-resistance or loss result.
Use changed readings as conditional evidence
If a suspected contact disappears after lifting, record both the electrical change and the mechanical change. That supports a state-dependent path; it does not prove when the path first existed. If a path appears only after a support is displaced, the new geometry must be considered before assigning it to the accident.
Likewise, a later high resistance cannot rule out an earlier intermittent contact. Heating, vibration and fault movement may change contact pressure or remove conductive debris.
References
- U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003.
- NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.
- Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, catalogue D004je, April 2020, specification and typical-property tables.