Calculate internal winding stress from local voltage differences under the measured terminal excitation. Winding capacitance, inductance and loss shape the transfer from each terminal to those internal nodes. [1]
Popov and colleagues compared terminal and internal measurements in a specially instrumented prototype. Its accessible nodes supplied validation that a normal field transformer generally does not expose. [1]

Use the actual terminal waveform as the excitation
Match polarity, reference, bandwidth and connected port conditions. Rao and Gajjar model repeated breaker events [2]; retain that terminal event train rather than substitute an unrelated ideal impulse.
For a validated linear transfer over its supported band, Vnode(ω) = Hnode(ω)Vterminal(ω). For two internal nodes i and j, the voltage difference is [Hi(ω) − Hj(ω)]Vterminal(ω). Node-to-ground voltage and insulation stress between neighboring nodes are therefore different outputs.
A multiport transformer requires the corresponding sum of port contributions. Omitting an excited or coupled port changes the inferred internal boundary.
Identify what validates the internal model
| Evidence | What it supports | What it does not establish alone |
|---|---|---|
| Terminal admittance | External port behavior in the measured band | Unique internal voltage distribution |
| Construction-based network | A physically motivated internal representation | Accuracy without parameter and response checks |
| Internal transfer measurements | Response at the accessible measured nodes | Every unmeasured location |
| Independent waveform comparison | Prediction under the challenged excitation | Unsupported frequencies or other configurations |
Verify internal identification and transfer bandwidth
Different internal networks can reproduce similar terminal admittance while predicting different local stresses. A successful terminal fit is consequently not proof that every internal element is identified.
Retain frequency-dependent losses and the measurement band used for the transfer model. Extrapolating a response peak beyond that band can create a precise but unsupported local voltage.
Check numerical realization and phase response when converting the frequency result to time. Matching transfer magnitudes alone does not guarantee the correct overlap of a repeated surge train.
Report the local quantity the evidence supports
Identify each predicted node or voltage difference, its model basis and uncertainty. Compare the relevant waveform with supported insulation evidence at that location rather than one terminal withstand number. [1]
Request transfer evidence for the internal node pairs controlling the insulation assessment. Apply the measured terminal waveform within that model’s validated band, and retain its uncertainty. Where the data cover terminals only, report the terminal exposure and specify the local transfer measurement still needed.
References
- M. Popov, R. P. P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Experimental and Theoretical Analysis of Vacuum Circuit Breaker Prestrike Effect on a Transformer, IEEE Transactions on Power Delivery 24, 2009. DOI: 10.1109/TPWRD.2009.2013383.
- B. Kondala Rao and G. Gajjar, Development and Application of Vacuum Circuit Breaker Model in Electromagnetic Transient Simulation, IEEE, 2006. DOI: 10.1109/POWERI.2006.1632503.