Trace virtual current chopping across the coupled phases. A reignition in one phase can drive a high-frequency component that cancels another phase’s power-frequency current and creates a forced current zero before its natural zero. [1]
Rao and Gajjar describe this interphase mechanism. [1] It requires the coupled three-phase circuit; three independent phase switches with no shared capacitive or other relevant paths cannot investigate it. Popov’s prototype measurements separately show why the resulting terminal waveform and internal winding response need distinct validation. [2]

Follow the initiating phase and the coupled paths
Identify the phase that first interrupts and subsequently reignites. That event can create a high-frequency current through source-side and load-side capacitances and other represented coupling paths. [1]
For another phase, write itotal(t) = ipower(t) + ihf(t). A forced zero occurs when these terms cancel. It is not the same event as ipower reaching its natural power-frequency zero.
The coupled current division depends on the actual circuit. An equal split into the two remaining phases is a limited symmetric example, not a general rule for unequal cables, capacitances or connections.
Use a signed three-phase waveform map
| Waveform or event | Evidence to retain | Question |
|---|---|---|
| Initiating-phase reignition | Gap voltage and renewed current | What launched the high-frequency component? |
| Other-phase currents | Total waveform and supported component separation | Was a zero forced while power-frequency current remained? |
| Interruption outcome | Quenching and subsequent gap recovery | Did the forced zero become a successful interruption? |
| Phase voltages | Signed phase-ground and phase-phase waveforms | Which insulation stress resulted? |
Verify quenching at the forced current zero
The breaker must be capable of extinguishing the current under the represented high-frequency conditions. If it continues conducting, the forced zero alone does not establish interruption. Model the quenching and gap-recovery behavior separately. [1]
Compare the timing across all phases. A coupled high-frequency zero occurring after the other poles have already completed interruption belongs to a different sequence from virtual chopping of still-conducting phases.
Retain sufficient measurement bandwidth and clock alignment to distinguish these intervals. Filtering can obscure the high-frequency component and make a forced zero appear to be an ordinary power-frequency event.
Evaluate the resulting voltage differences
Phase-ground peaks do not directly determine phase-phase peaks unless their timing and signs are retained. Opposite simultaneous excursions can create a larger difference, while separated peaks may not. Calculate the actual voltage difference waveform. [1]
Establish the sequence in the record: initiating-phase reignition, coupled high-frequency current, cancellation and successful interruption. A forced zero with no interruption evidence supports only the cancellation step. Calculate the resulting phase-ground and phase-phase waveforms from synchronized signed observations.
References
- B. Kondala Rao and G. Gajjar, Development and Application of Vacuum Circuit Breaker Model in Electromagnetic Transient Simulation, IEEE, 2006. DOI: 10.1109/POWERI.2006.1632503.
- M. Popov, R. P. P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Experimental and Theoretical Analysis of Vacuum Circuit Breaker Prestrike Effect on a Transformer, IEEE Transactions on Power Delivery 24, 2009. DOI: 10.1109/TPWRD.2009.2013383.