Represent multiple reignitions as successive circuit states. Each reconnection drives a high-frequency current and carries capacitor voltages and magnetic history into the next interruption attempt. [1]
Rao and Gajjar’s model treats dielectric recovery and high-frequency current quenching as separate breaker properties. Their historical typical parameters should not be mistaken for measurements of the breaker being studied. [2]

Represent the two competing conditions
After an interruption, the circuit creates a voltage across the gap while the gap’s dielectric strength recovers. A modeled breakdown occurs when the relevant stress exceeds the represented withstand condition. State the time reference and any statistical assumptions used by that condition. [2]
During renewed conduction, a current zero can occur at high frequency. Successful interruption also depends on the represented quenching capability and associated conditions. Automatically opening at every zero can manufacture a reignition sequence that the real breaker would not produce.
Keep an event-by-event ledger
| Transition | Condition to retain | State carried onward |
|---|---|---|
| Initial interruption | Current, timing and gap state | Transformer magnetic and capacitor states |
| Reignition | Gap voltage versus recovery model | Reconnected circuit and charge redistribution |
| High-frequency conduction | Current waveform and coupled paths | Updated electric and magnetic energy |
| Next interruption attempt | Zero crossing and quenching condition | State for the next recovery interval |
| Final interruption | Supported absence of further breakdown | Post-switch oscillation and decay |
Carry capacitor voltages and magnetic states continuously. Resetting them at reignition removes the accumulation mechanism. Use a circuit representation that does not create unphysical infinite impulses from ideal connections of charged elements. [2]
Compare event timing, current and gap voltage
Retain event count, intervals, current slopes, gap voltages and object-terminal response. Two parameter sets can produce the same highest voltage through different event sequences. Peak matching alone does not identify the breaker behavior. [2]
Check whether the measurement bandwidth could resolve the modeled intervals before comparing counts. Several fast events can merge into one apparent feature in a slower recorder.
Perform numerical convergence and supported parameter sensitivity checks. If random inputs are used, retain their basis, sampling method and seeds; a few selected runs cannot establish an occurrence probability.
Compare the simulated ledger with independent operations: event times, high-frequency currents, gap voltages and transformer-terminal response. Resolve a timing or quenching mismatch even when the peak voltage agrees. The accepted model should reproduce the sequence that creates the stress.
References
- M. Popov, R. P. P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Experimental and Theoretical Analysis of Vacuum Circuit Breaker Prestrike Effect on a Transformer, IEEE Transactions on Power Delivery 24, 2009. DOI: 10.1109/TPWRD.2009.2013383.
- B. Kondala Rao and G. Gajjar, Development and Application of Vacuum Circuit Breaker Model in Electromagnetic Transient Simulation, IEEE, 2006. DOI: 10.1109/POWERI.2006.1632503.