Voltage-transformer nonlinearity and acquisition faults can distort a secondary trace alongside genuine primary-circuit behaviour. Use independent observations to locate the response in the power circuit, sensor or recording chain. [1]
Jacobson’s examples treat voltage-transformer and station-service-transformer circuits separately. The nonlinear component involved in one case should not be assigned automatically to another. [2]

Locate the nonlinear and measurement boundaries
Identify the primary power transformer, voltage transformer, secondary burden and recorder input. Retain their connections and the phase reference. A voltage transformer has its own magnetic behavior and can lose its intended transfer relationship under conditions outside its supported range. [1]
Clipping in the recorder is a separate mechanism. A flat-topped display can result from input-range saturation even when the sensor output was not itself flat. Check channel status and the raw range before interpreting waveform shape.
| Evidence | Primary-circuit explanation | Measurement-chain explanation |
|---|---|---|
| Independent primary-voltage path | Supports an actual primary excursion if valid | Can expose disagreement with the original channel |
| Primary current and source state | Tests nonlinear response and supply path | May remain inconsistent with the indicated voltage |
| VT secondary burden and excitation | Part of the connected circuit where relevant | Tests transfer limitations or local nonlinear behavior |
| Acquisition range and bandwidth | Determines what is observable | Tests clipping, aliasing and overload recovery |
Compare simultaneous quantities
Where a valid independent primary-voltage measurement exists, compare its waveform with the expected secondary transfer, including polarity and timing. Retain both channels’ uncertainties and bandwidth. Agreement between channels sharing one sensor does not provide independent primary evidence.
Compare the power-transformer current and event topology with the candidate ferroresonant mechanism. A distorted secondary trace without a supported nonlinear supply circuit leaves the primary diagnosis incomplete.
Do not reconstruct missing primary peaks by multiplying a clipped secondary value by the nominal ratio. Once the channel has lost amplitude information, the exact primary peak is not available from that channel alone.
Keep a joint explanation available
A genuine primary disturbance can drive the voltage transformer outside its measurement boundary. The resulting trace can then contain both a physical event and additional transfer error. An either/or label may oversimplify the evidence.
Record the primary behaviour established independently and the remaining measurement-chain uncertainty. Investigate the sensor boundary wherever secondary distortion is the only confirmed observation.
References
- P. Ferracci, Schneider Electric, Ferroresonance, Cahier Technique No. 190, March 1998.
- D. A. N. Jacobson, Examples of Ferroresonance in a High Voltage Power System, IEEE PES General Meeting, 2003. DOI: 10.1109/PES.2003.1270499.