An Open Breaker Can Still Feed a Ferroresonant Circuit

  • Chenfan Power

Grading capacitors and stray contact capacitance can couple a live source to a downstream circuit after a breaker opens. Trace that capacitive path and the dissipative elements to assess whether energy can sustain a nonlinear transformer response. [1] [2]

Jacobson documents transformer and voltage-transformer cases fed through open-breaker grading capacitance. Their numerical capacitances are case data, not thresholds for every breaker or station.

An Open Breaker Can Still Feed a Ferroresonant Circuit: technical review table
Distinguish the two capacitor roles

Distinguish the two capacitor roles

A capacitance across an open contact connects the live-side and isolated-side potentials. Its sinusoidal current is jωCcontact(Vlive − Visolated). A capacitance from the isolated node to ground instead carries jωCground Visolated. Replacing the first with the second removes the source-coupling mechanism. [1]

Retain the actual pole states and conductor nodes. Several open breakers can supply parallel coupling paths, while bus-to-bus capacitance can add another route. The capacitance seen by one isolated bus need not equal a single break’s catalogue value.

Mapped branchConnectionRole in the study
Open-contact grading or stray capacitanceLive node to isolated nodeTransfers current and energy from the source
Isolated-node capacitance to groundIsolated conductor to reference groundChanges stored charge and circuit response
Mutual bus or phase capacitanceTwo non-ground conductor nodesCouples their evolving potentials
Transformer and connected loadActual winding and secondary pathsProvides nonlinear response and damping

Reconstruct what remains after interruption

Use the interruption sequence to establish the pre-existing capacitor voltages and transformer magnetic state. The open-state circuit can inherit energy from the preceding energized condition before continuing source input becomes important. [1]

A steady linear divider can estimate a limited unsaturated condition but cannot establish all nonlinear responses. The transformer magnetization and losses interact with the capacitive supply path; an abnormal state may coexist with a lower-voltage state under the same parameters.

Compare credible combinations of breaker poles, parallel devices and connected loads. A model that opens every capacitance branch when a breaker opens cannot investigate this mechanism.

Confirm the sustained energy-supply path

Identify the source port and follow its power transfer in the nonlinear simulation or supported event analysis. Distinguish stored-energy decay from a continuing supplied response. A high transient peak alone does not establish sustained ferroresonance. [1]

Retain uncertainty in grading and stray capacitance rather than assigning a generic value to every open pole. Layout and device construction can materially affect the path.

Map the coupling that supplies the nominally isolated circuit and the paths that dissipate energy. Use those paths to distinguish a sustained response from a transient discharge.

References

  1. P. Ferracci, Schneider Electric, Ferroresonance, Cahier Technique No. 190, March 1998.
  2. D. A. N. Jacobson, Examples of Ferroresonance in a High Voltage Power System, IEEE PES General Meeting, 2003. DOI: 10.1109/PES.2003.1270499.