Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Regulator Steps and Overshoot in AC Withstand Tests

  • Chenfan Power

Regulator steps, averaging delay and source-load dynamics shape the voltage trajectory applied during an AC withstand test. Check overshoot as well as the settled reading to establish the object’s actual exposure.

HIGHVOLT identifies the regulator and HV voltage measurement as separate components. Assess their closed-loop behavior using the actual object-voltage trace, rather than judging the result from the final setpoint alone. [1]

Regulator Steps and Overshoot in AC Withstand Tests: technical review table
Record the complete response interval

Record the complete response interval

Response itemEvidence to retain
Commanded changeStep or ramp amplitude and timing
Actuator behaviorDelay, movement and limits
Measured object voltagePeak, settling trajectory and waveform quality
Feedback processingAveraging window, filtering and update timing
Load conditionCapacitance, loss and any change during response

A controller reacting to an averaged voltage sees the event later than an instantaneous waveform recorder. Keep that processing delay in the timing model. Otherwise, apparent actuator hesitation may actually be measurement latency.

Interpret overshoot on the correct amplitude basis

For an illustrative linear second-order step response with damping ratio ζ below one, fractional overshoot is exp[−πζ/√(1 − ζ²)]. At assumed ζ = 0.4, this is about 25.4% of the commanded step amplitude.

If an idealized command changes voltage from 95 to 100 kV, the 5 kV step produces approximately 1.27 kV overshoot above the final value in that model. It does not predict a 25.4 kV excursion above 100 kV.

Actual systems can include deadband, discrete actuator steps, saturation and nonlinear source behavior. Their overshoot cannot be established from this formula without evidence that the model applies.

Test the load conditions that change the response

Capacitance changes the source’s voltage-regulation relationship. A controller response established on one object can therefore differ on another. Near a critical source-load condition, a small actuator increment can create a larger-than-expected object-voltage change.

Compare representative load boundaries and target-near commands under the approved characterization procedure. Retain initial regulator position and any limit reached. A test that starts far from the eventual operating position may not expose the same behavior as a final adjustment near the target.

Review the voltage trajectory against the required test basis, including relevant transient and steady criteria. Do not invent a permissible overshoot percentage from the illustrative dynamics.

Resolve excursions through the controller and source-load response, then verify the complete applied trajectory against the supported boundary. Retain measured peaks in the test record alongside the steady value.

Check the excursion against the declared test boundary

Retain the complete voltage-measuring transfer and uncertainty with the recorded trajectory [2].

For the assumed damping ratio 0.4, fractional second-order overshoot is 0.25383. A 95-to-100 kV step therefore reaches 101.269 kV in this model. Against an assumed project ceiling of 101.0 kV, the model exceeds the ceiling by 0.269 kV. Verify measured load-dependent dynamics and refine the command trajectory before relying on the settled reading.

References

  1. HIGHVOLT Prüftechnik Dresden GmbH, HVAC Test Systems Based on Transformers, 1.10/5 WP, November 2020.
  2. IEC, IEC 60060-2:2025, High-voltage test techniques — Part 2: Measuring systems.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing