Half-cycle saturation produces asymmetric current pulses. Terminal reactive power depends on voltage, phase and the selected power definition as well as the waveform. Measure those quantities together to compare the magnetic response with the electrical burden. [1]
The NERC thermal assessment white paper lists increased reactive demand among the effects of GIC. Turning that observation into a defensible measurement requires more than comparing peak current before and during an event.

Choose the quantity the comparison will report
For balanced sinusoidal terminal voltage and the fundamental current component, fundamental reactive power is Q1 = 3 Vphase,1 I1 sin φ1. Voltage and current are RMS quantities; φ1 is the fundamental current lag angle. The corresponding real power is P1 = 3 Vphase,1 I1 cos φ1.
Under unbalanced conditions, calculate the sum of the phase contributions instead. Under voltage distortion, state how the instrument treats harmonic reactive components. A meter’s displayed Q and a simulation’s fundamental Q1 may use different definitions.
Total RMS current includes harmonic components. Multiplying voltage by that current gives an apparent-power quantity under a stated convention, not automatically Q1. Similarly, √(S² − P²) can include distortion-related nonactive power and must not silently replace a fundamental reactive-power calculation.
Keep the terminal and load boundaries visible
| Boundary | Recorded quantity | Comparison rule |
|---|---|---|
| Transformer input | Synchronized phase voltages and currents | Same polarity, bandwidth and time window |
| Transferred load | Output power or a justified load estimate | Separate changing load from incremental transformer demand |
| DC excitation | Signed winding or effective DC current | Use the relevant connection conversion |
| Power processing | Q1, real power and harmonic metrics | Same definitions in meter and model |
| Operating state | Voltage, tap, loading and cooling | Identify changes across the event |
An increase at the input terminal can include the network load’s response to falling voltage. Even subtracting output Q needs care: the remaining quantity includes the transformer’s AC series reactive consumption as well as excitation demand. A matched operating baseline, or an explicit circuit model, is needed before attributing the whole difference to DC bias.
Apply the same calculation to the simulated waveform
Export modeled terminal voltage and current and process them with the same window and fundamental extraction used for the measurements. A model’s internal magnetizing branch current is not interchangeable with measured total terminal current.
Use a window long enough for a meaningful fundamental estimate but short enough to resolve changes in the DC input. Report the window duration alongside the result; otherwise, a brief saturation episode and a smoothed meter trace can appear inconsistent simply because they describe different intervals.
Compare fundamental reactive power with a peak-current impression
Assume balanced sinusoidal phase voltage 6.35 kV RMS, fundamental current 10 A RMS and lag angle 80°. Q1 = 187.61 kvar and P1 = 33.08 kW [2]. Add an assumed balanced fifth-harmonic current of 10 A RMS per phase while leaving that fundamental unchanged: total RMS becomes √(10² + 10²) = 14.14 A, 41.4% higher, but Q1 and P1 remain unchanged. Thus larger current alone does not quantify incremental Q1. Use the same terminal extraction and reference before separating transferred load, series consumption and excitation demand.
Compare incremental Q1, harmonic current and real-power changes separately. A mismatch in Q1 points to phase extraction, load transfer or source-voltage behaviour; resolve that boundary before adjusting a magnetic model to fit current peaks.
References
- NERC, Transformer Thermal Impact Assessment White Paper, Project 2013-03 Geomagnetic Disturbance Mitigation, October 2017.
- U.S. Department of Energy, DOE-HDBK-1011/3-92, Electrical Science, Volume 3, June 1992.