A wattmetric directional metric extracts a small active component from current that can be largely reactive. Rotating that current phasor through a measurement phase error transfers reactive current into the active projection. Build the complete channel uncertainty budget [1] on the relay’s documented scaling and direction.
Identify the relay’s actual quantities first. Residual voltage, calculated zero-sequence voltage, residual current and neutral CT current are related only through their defined connections and scaling. A factor-of-three mismatch can change a numerical threshold even when polarity appears correct.

State the product’s basis
If Ur = 3U0 and Ir = 3I0 are residual RMS phasors, the zero-sequence power component on the corresponding three-phase basis is P0 = (1/3)Re(UrIr*). Voltages are volts, currents amperes, the asterisk denotes complex conjugate and P0 is watts. A relay may use a differently scaled product or characteristic; use its documented basis rather than importing this factor by assumption.
Reference directions determine the sign. Reverse either measurement polarity and the directional product reverses. Reverse both and the product may retain its sign while other measurements or zone relationships remain wrong. Polarity testing must therefore verify each channel against the physical circuit, not only their combined product.
Estimate phase leakage before selecting a margin
With voltage chosen as the real reference and current written Ia + jIq, a small relative phase error δ can introduce an active-component error with magnitude approximately |Iqδ|. δ is in radians. Ratio errors also scale the product, but they do not replace this cross-component effect.
Assume a measured current with Ia = 2 A and Iq = 50 A and a relative phase error of 0.5 degree; this corresponds to 0.00873 rad and approximately 0.436 A of possible active-component leakage. That is about 22% of the assumed active current. This is an error sensitivity, not a protection setting or expected performance.
| Error contributor | What to retain | Effect on active evidence |
|---|---|---|
| CT and voltage-channel phase | Relevant burden, amplitude and frequency conditions | Reactive-to-active leakage |
| Polarity and reference direction | Primary path and relay convention | Directional sign |
| Ratio and residual scaling | 3U0/3I0 or other defined basis | Product magnitude |
| Timing/filter alignment | Processing behavior during the event | Additional relative phase or transient bias |
Test the least favorable credible measurement condition
Use the actual large-reactive/small-active cases from the network study. Apply credible joint channel uncertainties and the relay’s documented processing, preserving correlations where known. Treat polarity reversal separately from small random uncertainty; it is a wiring or convention defect.
If a switched resistor creates the active-current window, retain its actual connection and duration. The regulator manual documents resistor control and thermal restrictions [2]; an unavailable branch cannot supply the active increment assumed by the protection assessment.
Calculate the signed protection metric and its uncertainty for the relevant fault and non-fault states. Apply those results to the actual relay characteristic so the chosen settings retain a clear directional margin.
References
- B. N. Taylor and C. E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994, sections 5 and 6.
- A. Eberle GmbH & Co. KG, The Petersen-Coil Regulator, REG-DP/REG-DPA, including Current Injection and High Power Current Injection, Operating Instructions, April 2017.