A neutral-voltage resonance curve combines network unbalance, damping and the compensation characteristic. A strong, stable response supports a useful tuning fit; weak excitation or changing topology makes the fitted centre less certain. Read the curve together with the network state and electrical calibration. [1] [2]
Record neutral-voltage magnitude and phase, coil position, approach direction and feeder state on a common time basis.

Separate excitation from network response
An elementary equivalent gives Un = Iu/(G + jB). Un is neutral-displacement voltage in volts, Iu is the unbalance-source RMS phasor in amperes, G is aggregate conductance in siemens and B is net susceptance in siemens. For a simple parallel coil and capacitance, B = ωCΣ − 1/(ωL), with frequency and the effective compensation branch defined consistently.
If Iu and G stay constant through the sweep, |Un| = |Iu|/√(G² + B²). The magnitude reaches its maximum at B = 0 in this model. At B = +G or −G, the voltage is the peak divided by √2; these are the half-power points.
Their separation is 2G in susceptance units. It is not automatically 2G in coil-position units. Converting the width requires the measured position-to-susceptance relation, which may be nonlinear.
Keep the fitting assumptions beside the curve
| Curve observation | Possible interpretation | Assumption to check |
|---|---|---|
| Broad low peak | Greater damping or weaker excitation | Excitation remains known or sufficiently stable |
| Peak moves between sweeps | Changed capacitance, coil response or state | Feeder state and position calibration are comparable |
| Different forward/reverse traces | Direction dependence or changing excitation | Time drift is separated from approach direction |
| No resolvable peak | Insufficient observable response | Noise and natural unbalance are quantified |
A voltage magnitude alone cannot distinguish a reduced unbalance source from an increased conductance. Phase information and independent state evidence can help, but the fit must still state which quantities are assumed fixed or separately known.
Record topology throughout the tuning sweep
A feeder switch during the sweep changes the network being fitted. Background load-dependent coupling can also change the unbalance excitation without changing the aggregate earth capacitance. Treat those intervals as state changes rather than forcing one smooth curve through all readings.
Use repeat sweeps or appropriate injection-based evidence when the natural excitation is too weak or unstable to resolve the parameters. Selecting the largest noisy sample does not establish the resonance coordinate.
Report the fitted centre, damping and uncertainty beside the feeder configuration and coil calibration used in the sweep. Where the response is too weak to identify the parameters, obtain another observation or constraint before assigning a tuning position.
References
- A. Eberle GmbH & Co. KG, The Petersen-Coil Regulator, REG-DP/REG-DPA, including Current Injection and High Power Current Injection, Operating Instructions, April 2017.
- Q. Yang, B. Zhang, J. Ran, S. Chen, Y. He and J. Sun, Measurement of Line-to-Ground Capacitance in Distribution Network Considering Magnetizing Impedance’s Frequency Characteristic, Energies 10, 2017. DOI: 10.3390/en10040477.