Zero-sequence impedance, neutral topology and tolerance determine how parallel grounding transformers share current. Adding or removing a unit also changes the network fault response. Assess branch duty for normal service, credible unequal sharing and one-unit-out operation. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Identify whether each transformer has its own neutral impedance or whether their neutrals join before a shared grounding element. These configurations require different circuits. Copying a shared resistor into two independent branches would create a return network that does not exist.

Draw the parallel branches on the phase-current basis
Bus zero-sequence node V0
├─ transformer Z01 ─ individual neutral contribution 3Zn1 ─ reference
└─ transformer Z02 ─ individual neutral contribution 3Zn2 ─ reference
Shared neutral equipment, if present: draw once at the common node
For independent neutral branches in a linear symmetrical model, I0k = V0/(Z0k + 3Znk). V0 is the common phase zero-sequence voltage RMS phasor in volts, each Z is in ohms and I0k is amperes. The transformer neutral current is INk = 3I0k. The total branch contribution is the phasor sum, not necessarily the sum of current magnitudes.
The rest of the network determines V0. Branch division and total fault current should therefore be solved together. Adding a second transformer can reduce the equivalent zero-sequence impedance and increase the total contribution.
Expose tolerance-driven unequal duty
As an illustrative division only, suppose the two complete phase-basis branches are j1.0 and j1.2 ohm at the same frequency. Their currents have the same angle and the ratio I01/I02 is 1.2. If the total neutral contribution for this example is prescribed as 100 A, unit 1 carries approximately 54.55 A and unit 2 carries 45.45 A.
| Illustrative branch | Complete branch impedance | Neutral-current share |
|---|---|---|
| Unit 1 | j1.0 ohm | 54.55 A |
| Unit 2 | j1.2 ohm | 45.45 A |
The prescribed 100 A is not a predicted fault current or a rating. It simply makes the ratio visible. Complex branches with unequal resistive and reactive proportions require full phasor division; the same percentage arithmetic is then insufficient.
Remove one branch and solve again
For the one-unit-out case, update the connected network rather than assigning the old total automatically to the remaining transformer. Its current may increase, while the overall fault current and neutral displacement may also change. Recheck detection sensitivity, clearing duration and each remaining internal winding-section duty.
Use credible impedance tolerance combinations to identify the branch carrying the largest current. If nonlinear behavior or saturation changes impedance with current, iterate the coupled model rather than treating the tolerance as a constant multiplier.
Report all three duty cases beside the exact neutral topology. Identify the branch carrying the greatest current and the grounding function retained when one unit is unavailable.
Carry unequal sharing into individual ratings
Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].
For the assumed j1.0 Ω and j1.2 Ω complete branches, division of 100 A total neutral current gives 54.55 A and 45.45 A. Unit 1 carries 9.09% more than an equal 50 A allocation. Verify each branch against its own current envelope and recalculate total network fault current when either branch is removed.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.