When a grounding transformer closes onto an existing earth fault, the network may already have displaced neutral voltage and charged phase-to-earth capacitances. Model that initial state together with the unit’s magnetic state before introducing the new zero-sequence path. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Preserve the faulted network state, section flux and actual pole-closing sequence when comparing the two event orders.

Place the fault before the closing event
Model the connected network before the grounding transformer is available. Include its source, existing grounding paths, fault impedance, connected capacitances and loads. Solve or establish the faulted pre-connection state rather than starting all capacitor voltages from an unfaulted initialization.
The grounding transformer may initially be isolated, connected without its neutral return, or partly connected through other equipment. These are different starting topologies. State the actual one and retain any initial magnetic state supported by its preceding history.
| Study time | Event or state | State passed forward |
|---|---|---|
| Before fault | Original network topology | Operating voltages and stored energy |
| Fault inception | Fault location and impedance introduced | Displaced phase-to-earth voltage pattern |
| Before transformer closing | Fault persists for the defined interval | Capacitor voltages and faulted-source response |
| Transformer connection | Specified pole timing and neutral state | New current paths and flux evolution |
| Protection and clearing | Actual detection and interrupting behavior | Peak and accumulated duty before interruption |
Vary closing phase without erasing the initial state
A sinusoidal RMS voltage value alone does not determine the flux trajectory at connection. Closing phase, pre-existing flux and actual section induced voltages affect the first cycles. Use the winding connection to map terminal conditions into sections; a nominal line-to-line voltage does not describe every earth-referenced stress in a displaced network.
The neutral-current waveform may contain the fault contribution, an asymmetric magnetic response and capacitive redistribution. It should not be decomposed by simply adding independently chosen peak values if the components interact through the same nonlinear circuit. Retain synchronized phase currents, neutral current and relevant voltages in the simulation output.
For converter-supplied networks, include applicable current limiting and sequence-control behavior. A fixed ideal source behind an impedance can misrepresent the current that the actual converter supplies after the topology changes.
Inspect peaks and duration separately
Use peak section current and the associated leakage field for mechanical questions. Use the time integral of section-current squared, with the relevant resistance and loss model, for conductor heating. Check external grounding-device duty at its own current and voltage terminals. The same event output supports these questions, but one scalar result does not settle them all.
Compare fault-before-connection with connection-before-fault at matched network inputs and initialization. Use the resulting section currents and voltage trajectories to isolate the effect of event order.
Retain initial flux in fault energization
Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].
Assume one modelled limb begins at 0.30 T and receives a signed induced-voltage integral of 0.60 V·s through 100 turns and 0.010 m² effective area. The flux-density increment is 0.60/(100 × 0.010) = 0.60 T; the endpoint is 0.90 T for additive polarity or −0.30 T for opposite polarity. Sweep the initial state and switching phase before selecting the governing current waveform.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.