Magnetic History between Two Grounding Transformer Faults

  • Chenfan Power

The grounding transformer’s magnetic state carries across fault clearing and into a second fault. Record whether the unit remains energized, how its terminal excitation changes and which hysteretic state the first event leaves behind. Use that history to initialize the repeated-fault model. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Separate three cases: fault clearing with the transformer still energized, fault clearing that also removes its supply, and a topology change that alters its winding or neutral connections. The magnetic history after each case is different. A second-fault study must carry the relevant history forward rather than resetting the core state at the event boundary.

Magnetic History between Two Grounding Transformer Faults: technical review table
Build the two-fault timeline

Keep voltage integration continuous across clearing

For an identified section, the change in linked core flux is ΔΦ = (1/(sN))∫eind dt. Flux is in webers, eind is induced section voltage in volts, time is seconds, N is turns and s is the polarity sign. Resistive and leakage contributions must be separated according to the model. This relationship provides the flux change; hysteresis and the preceding magnetic state determine the absolute trajectory.

When the unit remains energized, compare the disturbance with the ongoing periodic baseline. A decaying asymmetric response may persist after current interruption, but it is not the same boundary condition as a disconnected winding with a retained remanent state. The clearing phase and actual voltage waveform matter more than a label saying fault removed.

Build the two-fault timeline

IntervalState to retainComparison for the next interval
Before fault 1Periodic excitation, connection and initial fluxReference magnetic cycle
Fault 1Section currents and induced voltagesDeparture from the reference trajectory
ClearingInterruption phase and switch topologyWhether supply and neutral path remain
Between faultsContinued excitation or disconnected hysteretic stateState actually reached at fault 2 inception
Fault 2Second inception phase and updated statePeak flux, asymmetric current and local field demand

For a clean comparison, vary the second inception phase while preserving the same first event. Then vary the inter-event interval. If both are changed together, an observed difference cannot be attributed specifically to magnetic recovery. A model may also need the cooling history, but magnetic and thermal state should remain separate variables.

Initialize a physically consistent limb-flux state

Limb fluxes are coupled by the actual core and return paths. In an ideal closed three-limb magnetic model, their signed relationship constrains their possible sum. Real external return paths can modify that simplified constraint. Choosing arbitrary independent remanent values for three limbs can create a state that the selected magnetic network cannot support.

Use a hysteretic magnetic representation whose state is generated by the preceding excitation, or identify a physically admissible initial-state range. A fixed linear inductance does not establish remanence simply because the simulation starts with a nonzero current.

Simulate fault 2 from the carried magnetic state and from a defined reference state. Retain the first-event conditions that explain any difference in peak flux or current so the repeated-fault margin can be reproduced.

Compare carried-state trajectories against the characterized excitation

Nippon Steel lists the 23ZH85 strip-loss ceiling as 0.85 W/kg at 1.7 T, 50 Hz after the stated specimen preparation [2]. That excitation point identifies the catalogue evidence; it is not a saturation limit. Keep the earthing-transformer connection and test boundary separate [3].

Assume a coupled magnetic model supplies two histories for one limb: initial flux densities of −0.35 T and +0.35 T. In each second event, assume the same signed 1.50 V·s induced-voltage integral through 100 turns and 0.010 m² effective area. The increment is 1.50 T; the endpoints are 1.15 T and 1.85 T. Resetting either history to zero would instead report 1.50 T and conceal a 0.35 T error.

The additive history reaches 0.15 T above the catalogue’s 1.7 T test point. Do not assign the catalogue loss to that asymmetric trajectory. Preserve the history producing 1.85 T and obtain an appropriate magnetic characteristic and waveform-dependent loss model before comparing repeated-fault margins. The example determines a flux-state difference, not a temperature or fault-current prediction.

Joint gaps, cutting stress, burr bridges, clamping and thermal processing influence the assembled magnetic response. Keep those manufacturing conditions matched when using measured core characteristics to initialize the model.

References

  1. D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
  2. Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, catalogue D004je, April 2020, specification and typical-property tables.
  3. IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.