Each voltage-reconnection mode has its own terminal phase relationship. Verify the selected winding sections, terminal references and phase displacement, then carry that identity into network compatibility and protection compensation studies. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Declare one phasor reference for every mode
Define the reference side, phase sequence, terminal names and observation direction. Use a consistent voltage quantity when comparing phase displacement. A line-to-line phasor should not be compared directly with a phase-to-neutral phasor without the applicable relationship; a delta port does not provide an accessible physical neutral merely because a model uses one.
| Mode record | Phasor data to preserve | Terminal data to preserve |
|---|---|---|
| Each completed voltage mode | Reference phasor and corresponding output phasor | Actual winding links and terminal allocation |
| Tap or alternate connection, where relevant | Magnitude and displacement in the same convention | Permitted state identity |
| External terminal adapter | End-to-end phase mapping and any reference change | Adapter and cable allocation |
| Protection representation | Compensation reference used by the function | CT locations, polarity and configured mode |
Record the phasor relationship for each mode
Consider a hypothetical identity table with mode A ratio 100 and displacement 0 degrees, and mode B ratio 50 and displacement 30 degrees, measured in the same declared terminal convention. The numbers are illustrative, not a design example inferred from a particular connection. They demonstrate that a correct voltage magnitude in mode B would not justify retaining mode A’s displacement in a system model.
Build the actual phasors from the approved winding and terminal drawings, then verify the relevant terminal relationships with applicable measurement evidence. Preserve sign and phase allocation rather than recording only a clock designation stripped of its reference.
Carry the selected identity into network and protection studies
Review the complete path from the mobile source terminals to the station connection. A cable adapter can permute phases even when the transformer’s internal displacement is correct. Distinguish physical terminal order from electrical phase sequence, especially when drawings face opposite directions.
Associate the mode identity with the model and protection parameters used for that deployment. A change in displacement can affect parallel-path compatibility and compensation; those consequences require the actual network and qualified protection assessment.
Accept each mode against its measured terminal phasors and the station’s reference convention. Keep that mode identity with the network model and protection data used for deployment.
Convert displacement into the model clock convention
Transformer differential compensation must preserve the selected winding connection and phasor references [2].
For the assumed 30° displacement in mode B, a 360° cycle divided into 12 clock positions gives 30° per position. A 30° lead and a 30° lag occupy different signed phasor positions despite the same magnitude. An assumed 1.0 per-unit reference maps to 0.8660 + j0.5000 or 0.8660 − j0.5000. Verify the measured sign before setting compensation.
References
- U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.
- B. Kasztenny, M. Thompson and N. Fischer, Schweitzer Engineering Laboratories, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.