Impedance across Reconnectable Transformer Voltage Modes

  • Chenfan Power

Voltage reconnection changes both the electrical base and, potentially, the leakage-field geometry of a mobile transformer. Use a measured or validated impedance for each physical winding arrangement, then convert that value to the base required by the system study. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Impedance across Reconnectable Transformer Voltage Modes: technical review table
Retain the physical mode with the test value

Retain the physical mode with the test value

Record energized and shorted terminals, winding links, tap, power base, voltage base, frequency and temperature. Identify where the impedance is referred. If winding sections change their electrical relationship, the leakage energy and current distribution can change even when the same copper remains inside the tank.

Illustrative modeSame-side voltage and power baseAssumed impedanceResulting impedance magnitude
A10 kV, 10 MVA0.40 ohm4.0 percent
B20 kV, 10 MVA1.80 ohm4.5 percent

For this assumed balanced three-phase, per-phase equivalent comparison, Zbase = VLL²/S is 10 ohms for mode A and 40 ohms for mode B. The results are 0.40/10 = 0.04 and 1.80/40 = 0.045 per unit. These are hypothetical measurements, not product data. Their difference cannot be explained away by copying one percent value across the modes.

Separate base conversion from reconnection physics

When only the reference base changes and the physical connection remains unchanged, a conventional per-unit conversion preserves physical ohms. When the connection changes, first obtain the appropriate physical equivalent for the new arrangement. Applying a base formula to the old equivalent assumes the very invariance that needs checking.

Retain resistance and reactance separately where the study needs them. The impedance magnitude alone does not establish X/R, losses or asymmetrical fault behavior. Also preserve temperature treatment and measurement uncertainty so that small mode differences are not overstated.

Use the mode map in the system studies

For each permitted mode and relevant tap, provide the equivalent impedance and its evidence boundary. Identify states that were measured, derived from validated design information or left unverified. The leakage-field analysis should account for which sections carry current and how their relative positions and connections affect the field.

Check voltage regulation, fault current and protection studies using the matched mode rather than a single fleet-wide impedance. A mobile unit may be mechanically suitable and have the correct voltage ratio while producing a different fault contribution in the selected configuration.

Complete the mode map with the missing test or justified design result. Use the resulting mode-specific impedance in regulation, fault-current and protection studies.

Reconcile both mode bases and physical ohms

Retain the tested winding, connection and measurement basis with the impedance comparison [2].

For the assumed 10 MVA modes, 10 kV gives a 10 Ω base and 20 kV gives 40 Ω. The corresponding assumed 0.40 Ω and 1.80 Ω equivalents are 4.0% and 4.5%. Holding 4.0% in mode B would imply 1.60 Ω, understating its stated impedance by 0.20 Ω or 11.1%. Use the mode-specific measured equivalent.

References

  1. U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.
  2. U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003, section 15.1.