A multi-voltage mobile transformer is ready when its completed power connection, selector position and protection/control indication agree. Verify that agreement for each reconnection mode, including incomplete positions and changes to the sensing or display chain. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Treat position and circuit identity as different evidence
Begin with the approved connection drawing for each mode. Identify which contacts or links establish that circuit and which mechanical features determine full engagement. Then identify how position is sensed. A label tells an operator what a position is intended to mean; an auxiliary contact reports a mechanical or control state; neither independently proves every power connection.
| State under review | Mechanical evidence | Electrical identity evidence | Interpretation |
|---|---|---|---|
| Fully established intended mode | Defined position and engagement confirmed | Connection-specific verification matches the drawing | The two evidence types agree for this mode |
| Intermediate or incomplete position | Position does not meet the defined completed state | Some intended contacts may be absent or ambiguous | No completed-mode identity can be inferred |
| Indication disagreement | Mechanical position and displayed mode differ | Circuit verification resolves the actual connection only within its scope | Treat the indication chain as unresolved |
| Correct display, wrong circuit allocation | Display alone appears valid | Mode-specific terminal relationship disagrees | The displayed name cannot override the electrical evidence |
| Loss of position signal | Current mechanical state not established by that signal | Any other evidence requires its own validated scope | Do not inherit the last valid indication automatically |
Cover ambiguous positions in the verification plan
Define how the design responds when a selector is between completed states, a sensor is stuck or a signal is lost. The relevant test is not merely whether each nominal display appears; it is whether an ambiguous position can be misreported as an established mode. Check signal coding, wiring allocation and the controller’s treatment of invalid combinations.
Use approved de-energized verification methods appropriate to the device to establish electrical identity. The measurements should distinguish the intended mode from credible wrong connections; a generic continuity result may be compatible with more than one circuit. This is a verification specification, not a field reconnection sequence.
Keep the mapping intact after relocation
Associate the approved mode drawing, selector identity, sensing channels and display text with the same configuration revision. Replacement indicators, harnesses or control modules can change the mapping without altering the power selector. Verify the affected mapping after such changes rather than relying on an old commissioning record.
Close the deployment check with the completed circuit, its mode drawing and the verified indication mapping. Keep the selector, harness and control revision together so the next move starts from a known electrical configuration.
Use ratio evidence to resolve a false position indication
Keep the ratio measurement tied to its tested winding and terminal references [2].
Assume the approved ratios are 20.0 in mode A and 10.0 in mode B. A 100 V, 50 Hz sinusoidal low-energy test at the declared input would yield 5.0 V and 10.0 V respectively in an ideal ratio screen. If the selector reports A but the measured output corresponds to B, retain the mismatch as an unresolved physical-state fault before energization.
References
- NASA, NASA Systems Engineering Handbook, section 6.5, Configuration Management, official online text.
- U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003, section 15.1.