Subsea variable-frequency duty combines voltage waveform, load and cooling state. Assess flux, converter-related losses and dielectric stress across those combinations to define the transformer procurement envelope. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Separate the fundamental from the waveform spectrum
For an ideal sinusoidal winding, Erms = 4.44 f N Φmax. With unchanged turns and geometry, the fundamental flux is proportional to E/f. Use the winding’s induced fundamental voltage, accounting for relevant drops, rather than assuming any terminal RMS measurement represents that quantity.
For sinusoidal excitation, the EMF relation supports the fundamental V/f comparison [2]. Converter harmonics, winding drops and cooling still require their own evidence.
| Envelope dimension | Quantity to retain | Why fundamental V/f is insufficient |
|---|---|---|
| Fundamental frequency and voltage | Actual induced fundamental and magnetic operating range | Resistance drop and waveform shape can alter flux |
| Harmonic spectrum | Current and voltage components by relevant frequency | AC winding resistance and stray losses vary with frequency |
| Switching waveform | Rise time, common-mode component and cable interaction | Terminal insulation duty differs from sinusoidal RMS duty |
| Load state | Current, power factor and motor operating condition | Electrical heating can change while V/f remains constant |
| Cooling boundary | Water temperature, local flow and internal circulation | Cooling capability does not follow frequency automatically |
Evaluate heating across the coupled operating envelope
Use frequency-dependent resistance where needed to estimate winding losses from the current spectrum. Do not sum harmonic current percentages and multiply a fundamental copper-loss value without examining the resistance at those frequencies. Include structural loss and voltage-related dielectric heating where the design requires them.
Check low-frequency/high-current, high-frequency/high-voltage and transient control states separately. Constant V/f can address one magnetic concern while leaving harmonic heating or terminal voltage stress unresolved. A frequency point qualified at one cooling boundary cannot automatically be used in colder, warmer or obstructed-water conditions without checking the relevant mechanisms.
Connect each frequency, voltage waveform, load and cooling combination to its supporting evidence. Issue that complete duty envelope with the procurement requirements.
Resolve the current consequence of constant volts per hertz
Assume a balanced three-phase, 2 MVA reference at 6.6 kV and 50 Hz with unchanged turns. At 30 Hz, unchanged voltage would raise V/f from 132 to 220 V/Hz. Constant V/f instead requires 3.96 kV, neglecting winding drops [2]. Keep the dielectric boundary identified separately [3].
Using S = √3VLLI [4], reference current is 175.0 A RMS. Delivering 2 MVA at 3.96 kV would require 291.6 A RMS, or 1.667 times that current. With assumed unchanged effective resistance, conductor loss would become 2.778 times its reference value. Holding current at 175.0 A instead limits this idealized apparent-power calculation to 1.20 MVA.
Specify current and cooling limits alongside the V/f schedule. Constant V/f alone does not justify maintaining the reference MVA at low frequency; the actual converter waveform and loss model determine the permitted duty.
References
- IEC/IEEE, IEC/IEEE 61886-2:2025, Subsea equipment — Part 2: Power transformers.
- B. Kasztenny, M. Thompson and N. Fischer, Fundamentals of Short-Circuit Protection for Transformers, 2012 revision.
- IEC, IEC 60076-3:2013+AMD1:2018, Power transformers — Part 3: Insulation levels, dielectric tests and external clearances in air.
- U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.