Keep phase-shifter terminal identities and wiring fixed when studying power reversal. Compare the changed current and internal duty across forward and reverse states with one traceable transformation convention. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
If a study reverses its from/to reference, translate the complete model. The equivalent complex-ratio and impedance placement need consistent treatment; negating one angle without the rest of the reference change can produce another physical device.

Compare forward and reverse states explicitly
| State field | Forward/reverse comparison | Evidence needed |
|---|---|---|
| Physical tap/topology | Same actual connection unless intentionally changed | Terminal and internal winding records |
| Power reference | Positive S-to-R versus negative S-to-R | Meter polarity and study sign declaration |
| Terminal voltage/current | Actual phasors under each operating condition | Reverse duty is not a mirrored scalar loading |
| Internal unit voltages/currents | Supported map for each direction and power factor | Local component limit may differ |
| Protection measurements | CT/VT references and compensation across the range | Security and sensitivity under both states |
| Control logic | Objective, sign and valid feedback | No assumed automatic sign reversal of a setpoint |
Separate a reference reversal from a physical reversal
For a declared two-port matrix Y and a port-permutation matrix P, a pure relabeling gives Ynew = PYPᵀ, with currents and voltages permuted consistently. That operation changes the representation, not the hardware.
Forward and reverse power at the original labels are instead different solved operating states of the same circuit. The internal current/voltage duty must follow those states. An ideal magnitude relationship cannot prove that all local losses and temperatures are symmetrical.
Carry power factor and terminal voltage
Use the actual reverse-power phasors, including reactive flow and voltage magnitude. A negative active-power value alone does not identify the complete current angle or component loading. Reverse flow can coincide with a different network operating point rather than an exact mirror of the forward one.
Retain the excitation and series-unit connections. Their internal relationships can depend on which terminal provides the relevant excitation reference and how the actual design regulates. Do not infer them from the word bidirectional.
Verify protection and control under both directions
Use qualified offline studies/tests for measurement compensation, external faults and directional feedback across the credited taps. Keep physical CT polarity distinct from a software power-sign convention.
Verify power reversal in one declared sign convention
PST application and test evidence must retain the stated terminal convention [2].
Assume equal terminal magnitudes, X = 0.25 per unit and signed effective angle changing from +5° to −5°. Lossless active power changes from +0.34862 to −0.34862 per unit. On an assumed 100 MVA base that is +34.86 MW to −34.86 MW. Confirm metering direction and controller sign at reversal instead of inferring them from a tap label.
References
- B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
- IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.