A furnace-transformer bushing interface can receive heat from both current crowding in the lead and its contact joint. A conductor’s AC resistance depends on its field boundary; an isolated-bar skin-effect estimate can miss the proximity field of a close return. Published slab-model experiments deliberately placed the return far away, so their isolated benchmark must be distinguished from this lead/return problem. [1]
Make the return field part of the loss calculation
Use a local wide-plate approximation: an outgoing plate and its opposite-current return are broad relative to thickness and spacing. Neglect edge fields and nearby steel. Magnetic field is approximately zero on the outside face and I/w at the facing surface. Solving the slab diffusion equation with that one-sided field gives Rac/Rdc = F(t/δ), where F(x) = x[sinh(2x) + sin(2x)]/[cosh(2x) − cos(2x)], δ = √[ρ/(πfμ₀)], and t is the plate thickness. The isolated symmetric slab instead uses F[t/(2δ)].
This boundary change matters: the same thickness does not imply the same effective resistance. Apply the approximation only where the plate width and paired-return arrangement justify it; terminal spreading and the three-phase installation need the actual field geometry.
Compare a thick lead with two paired thinner paths
Assumptions: 50 kA RMS at 50 Hz; 1 m active lead length; 400 mm width; either one 20 mm plate or two 10 mm plates with equal current sharing. Each thin path has its own matched return, and the pairs are separated enough to neglect cross-coupling. Both options contain the same outgoing copper area. Use assumed ρ₂₀ = 1.72 × 10⁻⁸ Ω·m and temperature coefficient 0.00393 K⁻¹.
Evaluate losses at the assumed limiting interface temperature of 75 °C. Then ρ₇₅ = 2.091778 × 10⁻⁸ Ω·m, δ = 10.294 mm and the outgoing-path equivalent Rdc = 2.615 μΩ. The one-sided resistance factors are 1.8319 for the 20 mm plate and 1.0766 for the paired 10 mm paths. Total outgoing copper loss I²RdcF is therefore 11.975 kW versus 7.037 kW, a 4.937 kW reduction. For the thick plate an isolated-slab estimate would instead give 7.037 kW and conceal that proximity penalty.
Apply the loss to the bushing-interface heat budget
Assume both layouts share a linear critical-interface thermal resistance of 0.002 K/W to a 40 °C cooling reference, with equal loss in the matched return and an additional 0.500 kW combined joint-loss input. Thermal resistance converts the source budget to the temperature difference. [2] At the 75 °C gate the available rejection is (75 − 40)/0.002 = 17.500 kW. Including outgoing and return losses plus the joints, the thick layout requires 24.449 kW and fails this screen; the split layout requires 14.575 kW and retains 2.925 kW of headroom.
Carry the paired thin layout forward, then verify finite-width current sharing, return placement, joints and local heat transfer at the bushing. The result depends on the assumed thermal path and field boundaries. A joint repair changes its own source; it cannot remove the lead’s proximity loss. Include temperature-dependent properties in the final coupled solution rather than treating this limit-temperature budget as a measured hotspot.
References
- P. Jabłoński and A. Bednarek, Analytical and Experimental Assessment of the Effect of Current Harmonics on the Heating of a Flat Rectangular Busbar, Energies 19, 4940, 2026. DOI: 10.3390/en19204940.
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.