Furnace phase impedance includes the short network’s conductor geometry, joints and mutual coupling. Decompose those external terms and the transformer equivalent to identify the source of measured current unbalance. IEEE C57.17-2012 is listed as Inactive-Reserved; use its furnace-transformer scope as a historical reference while specifying the contract acceptance basis. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Draw the actual three-wire or other secondary connection, including the arc return relationship. An unbalanced three-wire circuit cannot generally be solved by applying the same fixed phase voltage to three independent impedances: its floating node and coupling must be respected.

Decompose the short-network boundary
| Impedance contribution | Evidence to identify | Unbalance mechanism |
|---|---|---|
| Transformer terminal equivalent | Tap, base and winding connection | Internal voltage/impedance differences |
| Rigid conductors and joints | Phase routes, resistance and contact state | Unequal resistive drop and local heating |
| Flexible cables and electrode arms | Position-dependent length and geometry | Changing resistance/reactance with movement |
| Mutual inductive terms | Complete neighboring phase arrangement | Current distribution not captured by self terms alone |
| Arc/load boundary | Actual dynamic voltage-current relationship | Load asymmetry coupled to the network |
Keep Kirchhoff’s constraints in the example
Consider an illustrative linear three-wire star load with a floating node and balanced source phase voltages of 100 V RMS. Let total branch impedances, including a deliberately simplified linear arc substitute, be ZA = 4 + j2 mΩ, ZB = 4 + j3 mΩ and ZC = 4 + j2.5 mΩ. Mutual terms are omitted only for this example.
With source phasors VA, VB and VC, the floating-node voltage is Vn = (VA/ZA + VB/ZB + VC/ZC)/(1/ZA + 1/ZB + 1/ZC). Each branch current is Ik = (Vk − Vn)/Zk. The resulting magnitudes are approximately 22.32, 21.16 and 20.08 kA, and their phasor sum is zero.
These assumed values are not furnace operating data. A real arc requires an appropriate nonlinear/time-varying model, and an actual short network can require a full impedance matrix. The calculation demonstrates how external unequal terms create current asymmetry while respecting the return constraint.
Compare geometry across electrode positions
Retain conductor spacing and cable configuration at representative travel positions. Equal DC resistance does not establish equal AC impedance. Neighboring high-current routes can change proximity losses and mutual inductance as the geometry moves.
Use measurements with defined terminals and consistent frequency, temperature and current conditions. Strip out or model temporary test leads rather than treating them as installed network evidence.
When a phase discrepancy changes with cable position or an external joint correction, carry that result into the network model. When it persists at the transformer boundary, investigate the internal equivalent separately. The phase-by-phase decomposition prevents an external short-network difference from being hidden inside one transformer percentage impedance.
Use the same three-wire circuit for the comparison
Keep the preceding assumed floating-node connection and 100 V RMS phase sources, using a consistent winding-current reference [2]. As an algebraic control case, set all three total branch impedances to 4+j2.5 mΩ. The floating-node voltage is then zero and all current magnitudes are 100/√(0.004²+0.0025²) = 21.20 kA.
The preceding unequal case spans approximately 20.08–22.32 kA; this balanced control has no magnitude spread. It identifies the effect of the declared external total impedances while respecting ΣI = 0. Determine actual conductor, joint, coupling and arc contributions before selecting a physical correction.
References
- IEEE, IEEE C57.17-2012, IEEE Standard Requirements for Arc Furnace Transformers (Inactive-Reserved).
- U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.