Predicting Phase-Angle Slip During Motor-Bus Transfer

  • Chenfan Power

The relay sees a favorable angle and issues a command. While the breaker mechanism moves, the motor bus continues to slip relative to the alternate source. The relevant angle is the one at contact closure, not the earlier measured value. [1]

Prediction needs the relative frequency and its change over the delay. A fixed frequency difference may be adequate locally, but nonlinear motor rundown can invalidate it as the bus decays.

Predicting Phase-Angle Slip During Motor-Bus Transfer: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

Define the sign before calculating

Let δ be bus angle minus source angle, in radians. Let Δf be bus frequency minus source frequency, in hertz. Then dδ/dt = 2πΔf. If a = d(Δf)/dt is approximately constant over closing delay τ, the predicted angle is δpred = δ0 + 2πΔf0τ + πaτ². Time τ is in seconds and a is in hertz per second.

This is a local kinematic approximation. It assumes valid estimates and a sufficiently short interval for the stated acceleration model. It is not an approved relay setting or a guarantee of safe reconnection.

Prediction inputEvidence to retainError it can introduce
Present angleMeasurement reference and time stampOffset or stale initial state
Relative frequencyEstimator and valid voltage rangeLinear drift error
Changing slipModel/estimate and observation windowCurvature error
Breaker delayActual operating-condition rangeArrival-time error
Data latencySampling, processing and transportAdditional unmodeled prediction interval

Include the age of the estimate

A phasor result represents a measurement window, not an instantaneous point free of delay. Establish its effective time reference and include processing and communication latency where relevant. Otherwise the prediction can begin from a state that is already older than the assumed τ.

The SEL transfer paper discusses predicting angle over closing time and blocking excessive changing-slip conditions. Its specific implementation does not establish the estimator accuracy of another relay or installation.

Propagate a range, not one perfect point

Evaluate credible ranges for slip, acceleration and delay. Where their errors are correlated, do not combine them using an independence assumption without evidence. A conservative envelope may be more appropriate than a narrow statistical band.

Compare predicted arrival-angle ranges with actual recorded closure where such evidence exists. Retain unsuccessful predictions as well as favorable events; they reveal conditions in which the local model loses validity.

Record whether each estimator or timing uncertainty is a bound or a standard uncertainty before combining it. Sensitivity and correlation affect a combined uncertainty; they must match the selected arrival-angle model. [2]

Include changing slip in closure prediction

Assume initial relative angle 10°, relative frequency −2 Hz, frequency acceleration −5 Hz/s and delay 0.050 s. Arrival angle is 10 + 360(−2)(0.050) + 180(−5)(0.050²) = −28.25°. Constant-slip prediction gives −26°, differing by 2.25°. Compare the whole credible delay range before accepting the local approximation.

References

  1. P. Muralimanohar, D. Haas, J. R. McClanahan, R. T. Jagaduri and S. Singletary, Implementation of a Microprocessor-Based Motor Bus Transfer Scheme, IEEE PCIC, 2016, DOI: 10.1109/PCICON.2016.7589248.
  2. B. N. Taylor and C. E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994, sections 5 and 6.