Transformer overexcitation depends on voltage and frequency together. This video explains the volts-per-hertz basis for flux density and the effect of moving toward magnetic saturation. It connects the expected operating excursion with design induction, finished net steel area and the stacking factor achieved in production.

تنزيل الترجمة النصية

النص الكامل للفيديو
A smaller core can leave less room for overexcitation. With turns and net steel area fixed, flux density follows volts per hertz. Use the article's calculated examples. Start at one point seven zero tesla; ten percent higher volts per hertz gives about one point eight seven. Start at one point eight zero tesla; the same increase gives about one point nine eight. These are calculations, not test readings or a universal saturation boundary. Near saturation, magnetizing current can rise steeply, and stray flux can heat nearby metalwork. Choose the design from the expected operating excursion. Check the finished net steel area as well: production stacking factor changes the flux density the steel actually experiences.