Transformer Overload: Separate Core, Winding and Stray Losses
Sintesi tecnica
Transformer overload changes several heat sources. This video separates load-related winding and stray losses from the core's voltage-and-frequency-dependent magnetic duty. Core temperature must be reviewed with the complete thermal arrangement and the actual overload conditions.
Trascrizione
At overload, which losses are increasing? At unchanged supply voltage and frequency, core loss is essentially a baseline. Extra heating mainly comes from load losses in windings and structural parts. The article uses current at one point two times rated. A square-law estimate gives one point four four times the load loss, not total transformer loss. The core's baseline still contributes to the oil's heat budget. Lower no-load loss can leave more thermal margin. Overvoltage, distorted voltage, or a local core fault can change that picture. Compare total losses and cooling capability under actual operating conditions. Do not diagnose overload heating from a core-loss figure alone.