Chenfan Electric
Tiếng Việt
Gửi bản vẽ
Quay lại Video kỹ thuật

Thư viện video kỹ thuật

DC Bias and Harmonic Heating in Transformer Cores

Thời lượng 01:00 · 1920 × 1080

Tóm tắt kỹ thuật

DC bias and harmonics affect transformer cores through different mechanisms. This video separates an offset magnetic operating cycle from frequency-related loss and heating. Application review needs the actual waveform, operating conditions and the relevant magnetic and thermal evidence.

Tải phụ đề

Bản chép lời
A direct-current component can shift the core's magnetizing operating point. Alternating flux then swings around an offset centre. One half-cycle can move towards saturation, drawing sharply peaked magnetizing current. Noise, reactive demand and stray heating can increase. The flux return path matters, so core configuration and design flux density belong in the assessment. Now separate two harmonic cases. Distorted supply voltage can distort core flux and increase steel losses. Harmonic load current mainly adds heating in windings and structural parts. These are different mechanisms. Near HVDC links, converter plants or other possible DC sources, describe the actual network conditions in the enquiry. Assess the transformer for those conditions.

Yêu cầu về dự án

Liên hệ đội ngũ của chúng tôi ↗
Chenfan Electric

Trao đổi trực tiếp

Bắt đầu trao đổi.

Trao đổi về bản vẽ, nhu cầu vật liệu hoặc dự án.

Gửi bản vẽ