Raccolta di video tecnici
Choosing CRGO Grade for the Complete Transformer Core Build
Sintesi tecnica
CRGO grade selection belongs to the complete transformer core build. This video compares conventional grain-oriented, high-permeability and domain-refined material while considering joints, cutting, clamping, sheet thickness and stacking factor. It also explains why the intended annealing process and coil-traceable certificate need to match the selected material.
Trascrizione
Paying for domain-refined steel does not guarantee a low-loss finished core. Start with the material families: conventional grain-oriented steel, high-permeability steel, and domain-refined high-permeability steel. Refinement subdivides the magnetic domains. But joints, cutting stress and clamping stress still affect the finished core. Thinner sheets also change sheet count, edge length and the stacking factor. Check the complete build before upgrading the grade. Match the material to the design flux density and the agreed loss requirement. Confirm the intended annealing process is compatible with the refinement method. Then require a mill certificate traceable to the coil, and verify that the core builder can control joints, burrs and stacking.