Magnetostriction links electrical-steel magnetization with transformer core vibration. This video explains why a symmetric alternating cycle can produce a twice-frequency mechanical response. It also shows why the resulting sound depends on the core structure, clamping and the paths that transmit vibration.

Descargar subtítulos

Transcripción
A transformer can meet electrical requirements and still need a noise investigation. Magnetostriction makes the steel change length slightly as it magnetizes. Reversing flux does not reverse that length change. The article identifies twice line frequency: one hundred hertz on a fifty hertz network, or one hundred twenty on sixty, plus harmonics. The motion shown here is slowed and exaggerated. Flux crowding at joints, compressive stress and damaged tension coating can increase the source. Loose sheets can add rattle. A structural resonance near those excitation frequencies can amplify vibration. Consider flux density and joint quality, preserve coating, avoid handling bends, and clamp evenly to the design. Check natural frequencies as part of the noise investigation.