WEBVTT 00:00:00.452 --> 00:00:02.612 An unusual excitation current is a 00:00:02.627 --> 00:00:03.897 reason to investigate, 00:00:04.085 --> 00:00:05.942 not a diagnosis by itself. 00:00:06.808 --> 00:00:07.597 At no load, 00:00:07.733 --> 00:00:09.697 joint gaps and step-lap errors can 00:00:09.712 --> 00:00:11.582 increase the magnetic effort needed. 00:00:12.446 --> 00:00:14.840 Low stacking factor and mechanical stress 00:00:14.855 --> 00:00:16.400 can also change the result. 00:00:17.251 --> 00:00:18.587 After winding assembly, 00:00:18.735 --> 00:00:20.749 inspect the rebuilt top-yoke joints. 00:00:21.600 --> 00:00:23.512 Compare the current with the calculation 00:00:23.527 --> 00:00:24.277 for that core, 00:00:24.478 --> 00:00:25.752 then with other units of the 00:00:25.767 --> 00:00:26.647 same design. 00:00:27.511 --> 00:00:29.228 Review the phase pattern rather than 00:00:29.243 --> 00:00:30.918 forcing every phase to match. 00:00:31.769 --> 00:00:33.392 For later field comparisons, 00:00:33.488 --> 00:00:35.062 preserve a baseline taken with the 00:00:35.077 --> 00:00:36.491 same method, connection, 00:00:36.639 --> 00:00:38.470 tap position and test voltage. 00:00:39.334 --> 00:00:41.585 Use excitation current alongside loss 00:00:41.600 --> 00:00:43.053 results and build records. 00:00:43.892 --> 00:00:46.207 One catalogue range cannot explain every 00:00:46.222 --> 00:00:46.699 core.