WEBVTT 00:00:00.452 --> 00:00:02.999 At overload, which losses are increasing? 00:00:03.853 --> 00:00:06.269 At unchanged supply voltage and frequency, 00:00:06.392 --> 00:00:08.353 core loss is essentially a baseline. 00:00:09.217 --> 00:00:11.181 Extra heating mainly comes from load 00:00:11.196 --> 00:00:13.548 losses in windings and structural parts. 00:00:14.386 --> 00:00:16.155 The article uses current at one 00:00:16.170 --> 00:00:17.545 point two times rated. 00:00:18.410 --> 00:00:20.270 A square-law estimate gives one point 00:00:20.285 --> 00:00:21.894 four four times the load loss, 00:00:21.978 --> 00:00:23.704 not total transformer loss. 00:00:24.569 --> 00:00:26.676 The core's baseline still contributes to 00:00:26.691 --> 00:00:27.884 the oil's heat budget. 00:00:28.748 --> 00:00:30.491 Lower no-load loss can leave more 00:00:30.506 --> 00:00:31.465 thermal margin. 00:00:32.329 --> 00:00:34.355 Overvoltage, distorted voltage, 00:00:34.517 --> 00:00:35.921 or a local core fault can 00:00:35.936 --> 00:00:37.038 change that picture. 00:00:37.902 --> 00:00:40.478 Compare total losses and cooling capability 00:00:40.493 --> 00:00:42.532 under actual operating conditions. 00:00:43.397 --> 00:00:45.413 Do not diagnose overload heating from 00:00:45.428 --> 00:00:46.868 a core-loss figure alone.