WEBVTT 00:00:00.452 --> 00:00:02.481 A direct-current component can shift the 00:00:02.496 --> 00:00:04.653 core's magnetizing operating point. 00:00:05.519 --> 00:00:07.666 Alternating flux then swings around an 00:00:07.681 --> 00:00:08.600 offset centre. 00:00:09.452 --> 00:00:11.933 One half-cycle can move towards saturation, 00:00:12.082 --> 00:00:14.446 drawing sharply peaked magnetizing current. 00:00:15.298 --> 00:00:17.783 Noise, reactive demand and stray heating 00:00:17.798 --> 00:00:18.561 can increase. 00:00:19.399 --> 00:00:21.087 The flux return path matters, 00:00:21.261 --> 00:00:23.356 so core configuration and design flux 00:00:23.371 --> 00:00:25.176 density belong in the assessment. 00:00:26.027 --> 00:00:28.327 Now separate two harmonic cases. 00:00:29.191 --> 00:00:31.377 Distorted supply voltage can distort core 00:00:31.392 --> 00:00:33.288 flux and increase steel losses. 00:00:34.139 --> 00:00:36.429 Harmonic load current mainly adds heating 00:00:36.444 --> 00:00:38.431 in windings and structural parts. 00:00:39.269 --> 00:00:41.100 These are different mechanisms. 00:00:41.952 --> 00:00:43.483 Near HVDC links, 00:00:43.553 --> 00:00:45.778 converter plants or other possible DC 00:00:45.793 --> 00:00:47.939 sources, describe the actual network 00:00:47.954 --> 00:00:49.368 conditions in the enquiry. 00:00:50.233 --> 00:00:51.963 Assess the transformer for those 00:00:51.978 --> 00:00:52.741 conditions.