WEBVTT 00:00:00.452 --> 00:00:01.961 A smaller core can leave less 00:00:01.976 --> 00:00:03.585 room for overexcitation. 00:00:04.452 --> 00:00:06.012 With turns and net steel area 00:00:06.027 --> 00:00:08.382 fixed, flux density follows volts per 00:00:08.397 --> 00:00:08.887 hertz. 00:00:09.725 --> 00:00:12.350 Use the article's calculated examples. 00:00:13.202 --> 00:00:14.801 Start at one point seven zero 00:00:14.816 --> 00:00:15.319 tesla; 00:00:15.532 --> 00:00:17.171 ten percent higher volts per hertz 00:00:17.186 --> 00:00:18.795 gives about one point eight seven. 00:00:19.660 --> 00:00:21.077 Start at one point eight zero 00:00:21.092 --> 00:00:21.608 tesla; 00:00:21.769 --> 00:00:23.330 the same increase gives about one 00:00:23.345 --> 00:00:24.225 point nine eight. 00:00:25.090 --> 00:00:26.439 These are calculations, 00:00:26.522 --> 00:00:28.486 not test readings or a universal 00:00:28.501 --> 00:00:29.837 saturation boundary. 00:00:30.702 --> 00:00:33.121 Near saturation, magnetizing current can 00:00:33.136 --> 00:00:35.140 rise steeply, and stray flux can 00:00:35.155 --> 00:00:36.465 heat nearby metalwork. 00:00:37.316 --> 00:00:39.137 Choose the design from the expected 00:00:39.152 --> 00:00:40.527 operating excursion. 00:00:41.379 --> 00:00:43.030 Check the finished net steel area 00:00:43.045 --> 00:00:43.574 as well: 00:00:43.709 --> 00:00:45.960 production stacking factor changes the flux 00:00:45.975 --> 00:00:48.379 density the steel actually experiences.