WEBVTT 1 00:00:00.453 --> 00:00:01.941 A cool surface can hide a 2 00:00:01.956 --> 00:00:03.120 hotter core centre. 3 00:00:03.994 --> 00:00:05.747 Heat moves more easily along each 4 00:00:05.762 --> 00:00:07.631 sheet than across the coated stack. 5 00:00:08.488 --> 00:00:10.189 A larger limb makes the escape 6 00:00:10.204 --> 00:00:11.088 path longer. 7 00:00:11.972 --> 00:00:14.266 Compare equal lengths of circular limbs, 8 00:00:14.446 --> 00:00:15.880 with the same loss per unit 9 00:00:15.895 --> 00:00:16.394 volume. 10 00:00:17.278 --> 00:00:18.335 Double the diameter: 11 00:00:18.502 --> 00:00:20.782 heat generation becomes four times greater, 12 00:00:20.988 --> 00:00:22.910 but the side surface only doubles. 13 00:00:23.794 --> 00:00:25.601 Cooling ducts split the stack into 14 00:00:25.616 --> 00:00:27.955 thinner packets, bringing oil closer to 15 00:00:27.970 --> 00:00:28.841 the interior. 16 00:00:29.712 --> 00:00:31.745 Spacers must keep those ducts open 17 00:00:31.760 --> 00:00:33.899 after clamping, without concentrating 18 00:00:33.914 --> 00:00:34.506 pressure. 19 00:00:35.377 --> 00:00:37.702 Each duct also removes space available 20 00:00:37.717 --> 00:00:38.469 for steel. 21 00:00:39.353 --> 00:00:41.412 Duct positions, flow paths and net 22 00:00:41.427 --> 00:00:43.367 steel section must therefore be designed 23 00:00:43.382 --> 00:00:43.961 together. 24 00:00:44.845 --> 00:00:47.237 A surface reading alone cannot establish 25 00:00:47.252 --> 00:00:48.468 the centre temperature.